SYSE.13:5 - Worked Case: Pump-Controller Variants and Ten Installed Units

A pump manufacturer is deciding which of ten installed controllers may receive a cold-start protection change. The first export gives all ten the same product number and the status current. Inspection results and source records show four different decision-relevant groups:

Installed unitsObserved configurationEffect on the release decision
S001–S004Input board IO-A and the older installed firmware realization.Outside the candidate firmware package’s hardware compatibility claim.
S005Input board IO-B and temperature sensor TS-2, but no current sensor calibration evidence.Possible candidate after calibration evidence; not currently eligible.
S006–S008IO-B, TS-2, current calibration evidence, and an installed realization corresponding to the supported firmware lineage.May enter the current release comparison, subject to installation and verification Work.
S009–S010IO-B and TS-2; the database says installed, but current calibration evidence is absent.Possible candidates after the missing evidence is obtained; status alone is insufficient.

The candidate firmware package describes support for IO-B. To establish that a controller has the corresponding installation, use evidence identifying what was installed in that unit. A claim about what ran during operation also needs observations that cover that use.

A query of a competent CM arrangement could return these groups with their evidence and applicability; that would be sufficient for this configuration question. Here the existing records supply the unit and inspection facts, but the export does not supply the correspondence between the two bills of material. The engineer compares checking that correspondence once with maintaining a reusable relation for later queries. For this one-off ten-unit comparison, the team accepts the manual checking effort and keeps the checked correspondence with its existing change account. It does not undertake continuing mapping maintenance without a use that justifies it. Both alternatives need the same calibration and installation evidence.

The engineering and manufacturing bills of material use different item boundaries. The checked directional mapping relates the engineering board item to the manufacturing board-and-harness items. It loses installation-routing detail and cannot be used in reverse without another check. A changed bill or later reuse therefore needs its applicability checked. The engineer does not designate every fastener or database row as a configuration item because those differences cannot change this release.

The effectivity proposal names S006–S008, the supported operating-temperature conditions, the candidate package edition, and the required installation and verification Work. S001–S004 are excluded; S005 and S009–S010 retain explicit evidence gaps. A selected reference configuration supports comparison but does not claim that every installed unit realizes it.

The configuration basis can inform SYSE.14 and bound the integration Work in SYSE.11. A claim that installation occurred or operation succeeded needs evidence for that unit and use. Permission and release require decisions under the applicable authority. A changed board, sensor, package edition, calibration source, inspection, or release question reopens only the affected unit and correspondence claims.

When the full pattern is unnecessary. If a laboratory engineer needs only to know whether one already identified controller contains IO-B at the current inspection time, direct System, structure, temporal, and evidence patterns answer the question. A product-family configuration basis adds no value.